3.1.25.1 - Discharge Air Static Pressure Setpoint Can Be Decreased (Reset)

Summary

Most of the VAV box damper positions are less than a high damper limit, indicating an opportunity to decrease fan static pressure. Fan static pressure reset is required by ASHRAE Standard 90.1 - Section 6.5.3.2.3 VAV Set-Point Reset.

Root Cause

Fan static pressure setpoint reset sequence is not programmed or is overridden - Static pressure setpoint is set too high