3.1.31.1 - Majority Of VAV's In Heating Mode

Summary

The majority of the VAV's served by this air handling unit are in heating mode, indicating the discharge air temperature should be increased.

Root Cause

Discharge air temperature setpoint has been overridden - Improper discharge air temperature setpoint programming - High demand VAV's are calling for cooling and should be investigated for issues and being undersized