3.1.37.1 - Low Temperature Differential Across Cooling Coil

Summary

This unit is in cooling mode and has a low temperature decrease across the cooling coil with the valve open, indicating a failed cooling valve, actuator, or coil. This may lead to increased operating costs and comfort complaints.

Root Cause

Failed cooling valve or actuator - Damaged, plugged, or dirty coil - Mixed air or discharge air temperature sensor failure