3.1.7.1 - Percent Outside Air Calculated Is Less Than Outside Air Damper Command

Summary

The calculated outside air percent is less than the outside air damper command minus a threshold, indicating the actual damper position is less than the command. Calculated OA% = 100 X (RaTemp-MaTemp) / (RaTemp-OaTemp)

Root Cause

Stuck damper - Loose/broken linkages - Bad sensors

Inputs
Constants

launchpad@resolutebi.com